Siemens 3RT6026-1AG20 коммутационное устройство

Siemens 3RT6026-1AG20
SIEMENS · SIRIUS 3RT6026

Contactor AC 110 V 50/60 HZ AC3 11 kW 400 V AUX contacts 1 NO +1 NC 3-pole, size S0 screw terminal

Технические характеристики 3RT6026-1AG20

Технические данные Siemens 3RT6026-1AG20
ПараметрЗначение
Siemens 3RT6026-1AG20Contactor AC 110 V 50/60 HZ AC3 11 kW 400 V AUX contacts 1 NO +1 NC 3-pole, size S0 screw terminal
Сведения об изделии
product brand nameSIRIUS
product designationPower contactor
product type designation3RT6
General technical data
size of contactorS0
product extension auxiliary switchYes
power loss [W] for rated value of the current
at AC in hot operating state per pole1.9 W
without load current share typical2.62 W
type of calculation of power loss current-dependentquadratic
insulation voltage rated value690 V
degree of pollution3
surge voltage resistance rated value6 kV
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1400 V
shock resistance at rectangular impulse
at AC8,3 g / 5 ms, 5,3 g / 10 ms
shock resistance with sine pulse
at AC13,5 g / 5 ms, 8,3 g / 10 ms
mechanical service life (operating cycles)
of contactor typical10 000 000
of the contactor with added auxiliary switch block typical10 000 000
Substance Prohibitance (Date)05/01/2012
Net Weight0.39 kg
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
during operation-25 ... +60 °C
during storage-55 ... +80 °C
Main circuit
number of poles for main current circuit3
number of NO contacts for main contacts3
number of NC contacts for main contacts0
operating voltage
at AC-3 rated value maximum690 V
at AC-3e rated value maximum690 V
operational current
at AC-1 up to 690 V
at ambient temperature 40 °C rated value40 A
at ambient temperature 60 °C rated value35 A
at AC-3
at 400 V rated value25 A
at 690 V rated value13 A
at AC-3e
at 400 V rated value25 A
at 690 V rated value13 A
connectable conductor cross-section in main circuit at AC-1
at 60 °C minimum permissible10 mm²
at 40 °C minimum permissible10 mm²
operational current for approx. 200000 operating cycles at AC-4
at 400 V rated value9 A
at 690 V rated value9 A
operating power
at AC-1
at 230 V rated value13.3 kW
at 230 V at 60 °C rated value13.3 kW
at 400 V at 60 °C rated value23 kW
at 690 V at 60 °C rated value40 kW
at AC-3
at 230 V rated value5.5 kW
at 400 V rated value11 kW
at 690 V rated value11 kW
at AC-3e
at 230 V rated value5.5 kW
at 400 V rated value11 kW
at 690 V rated value11 kW
operating power for approx. 200000 operating cycles at AC-4
at 400 V rated value4.4 kW
at 690 V rated value7.7 kW
no-load switching frequency
at AC5 000 1/h
operating frequency
at AC-1 maximum1 000 1/h
at AC-3 maximum750 1/h
at AC-3e maximum750 1/h
at AC-4 maximum250 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC
control supply voltage at AC
at 50 Hz rated value110 V
at 60 Hz rated value110 V
operating range factor control supply voltage rated value of magnet coil at AC
at 50 Hz0.8 ... 1.1
at 60 Hz0.85 ... 1.1
apparent pick-up power of magnet coil at AC
at 50 Hz81 VA
at 60 Hz79 VA
inductive power factor with closing power of the coil
at 50 Hz0.72
at 60 Hz0.74
apparent holding power of magnet coil at AC
at 50 Hz10.5 VA
at 60 Hz8.5 VA
inductive power factor with the holding power of the coil
at 50 Hz0.25
at 60 Hz0.28
Auxiliary circuit
number of NC contacts for auxiliary contacts instantaneous contact1
number of NO contacts for auxiliary contacts instantaneous contact1
operational current at AC-12 maximum10 A
operational current at AC-15
at 230 V rated value10 A
at 400 V rated value3 A
at 690 V rated value1 A
operational current at DC-12
at 24 V rated value6 A
at 110 V rated value3 A
at 220 V rated value1 A
operational current at DC-13
at 24 V rated value6 A
at 110 V rated value1 A
at 220 V rated value0.3 A
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
yielded mechanical performance [hp] for 3-phase AC motor at 460/480 V rated value15 hp
Short-circuit protection
design of the fuse link
for short-circuit protection of the main circuit
with type of coordination 1 requiredgL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 100 A
with type of coordination 2 requiredgL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
for short-circuit protection of the auxiliary switch requiredfuse gL/gG: 10 A
Installation/ mounting/ dimensions
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening method side-by-side mountingYes
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
height85 mm
width45 mm
depth97 mm
required spacing
with side-by-side mounting
at the side0 mm
Connections/ Terminals
type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control circuitscrew-type terminals
type of connectable conductor cross-sections for main contacts
solid or stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
finely stranded with core end processing2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
type of connectable conductor cross-sections
for auxiliary contacts
solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
Safety related data
product function mirror contact according to IEC 60947-4-1Yes
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Further information
last modified:4/4/2026
Date 4/8/2026Subject to change without notice © Copyright Siemens 2026