Siemens 3RH6131-1AF00 коммутационное устройство

Siemens 3RH6131-1AF00
SIEMENS · SIRIUS 3RH6131

Contactor relay, 3 NO + 1 NC, AC 110 V, 50/60 Hz, size S00, screw terminal

Технические характеристики 3RH6131-1AF00

Технические данные Siemens 3RH6131-1AF00
ПараметрЗначение
Siemens 3RH6131-1AF00Contactor relay, 3 NO + 1 NC, AC 110 V, 50/60 Hz, size S00, screw terminal
Сведения об изделии
product brand nameSIRIUS
product designationContactor relay
product type designation3RH6
General technical data
size of contactorS00
product extension auxiliary switchYes
power loss [W] for rated value of the current without load current share typical1.05 W
insulation voltage with degree of pollution 3 at AC rated value690 V
surge voltage resistance rated value6 kV
shock resistance at rectangular impulse
at AC7,3 g / 5 ms, 4,7 g / 10 ms
shock resistance with sine pulse
at AC11,4 g / 5 ms, 7,3 g / 10 ms
mechanical service life (operating cycles)
of contactor typical30 000 000
of the contactor with added auxiliary switch block typical10 000 000
Substance Prohibitance (Date)05/01/2012
Net Weight0.22 kg
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
during operation-25 ... +60 °C
during storage-55 ... +80 °C
Main circuit
no-load switching frequency
at AC10 000 1/h
at DC10 000 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC
control supply voltage at AC
at 50 Hz rated value110 V
at 60 Hz rated value110 V
operating range factor control supply voltage rated value of magnet coil at AC
at 50 Hz0.8 ... 1.1
at 60 Hz0.85 ... 1.1
apparent pick-up power of magnet coil at AC37 VA
inductive power factor with closing power of the coil0.8
apparent holding power of magnet coil at AC5.7 VA
inductive power factor with the holding power of the coil0.25
Auxiliary circuit
number of NC contacts for auxiliary contacts1
number of NO contacts for auxiliary contacts3
identification number and letter for switching elements31 E
operational current at AC-12 maximum6 A
operational current at AC-15
at 230 V rated value10 A
at 400 V rated value3 A
at 690 V rated value1 A
operational current at 1 current path at DC-12
at 24 V rated value6 A
at 110 V rated value3 A
at 220 V rated value1 A
operational current with 2 current paths in series at DC-12
at 24 V rated value6 A
at 110 V rated value4 A
at 220 V rated value2 A
operational current with 3 current paths in series at DC-12
at 24 V rated value6 A
at 110 V rated value6 A
at 220 V rated value3.6 A
operating frequency at DC-12 maximum1 000 1/h
operational current at 1 current path at DC-13
at 24 V rated value6 A
at 110 V rated value1 A
at 220 V rated value0.3 A
operational current with 2 current paths in series at DC-13
at 24 V rated value6 A
at 110 V rated value1.3 A
at 220 V rated value0.9 A
operational current with 3 current paths in series at DC-13
at 24 V rated value6 A
at 110 V rated value3 A
at 220 V rated value1.2 A
operating frequency at DC-13 maximum1 000 1/h
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 VC characteristic: 6 A; 0.4 kA
design of the fuse link for short-circuit protection of the auxiliary switch requiredfuse gL/gG: 10 A
Installation/ mounting/ dimensions
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening methodscrew and snap-on mounting onto 35 mm DIN rail
height57.5 mm
width45 mm
depth73 mm
Connections/ Terminals
type of electrical connection for auxiliary and control circuitscrew-type terminals
type of connectable conductor cross-sections
for auxiliary contacts
solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Safety related data
product function positively driven operation according to IEC 60947-5-1Yes
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Further information
last modified:4/4/2026
Date 4/6/2026Subject to change without notice © Copyright Siemens 2026

Разрешения и сертификаты

General Product Approval Maritime application other
Environment

Техническая документация по 3RH6131-1AF00